Features At a Glance:

  • ETL listed to UL 1995
  • 1,200 to 12,000 CFM
  • Custom Designed & Built DX Coils
  • Multiple Fan Type Options
  • Multiple Accessory and Control Options
  • Custom Configurations and Dimensions
  • Factory Wired and Piped Commercial and
    Industrial Condensing Units Available
    with Digital Scroll Compressor


  • Packaged Direct Fired and DX Cooling Units

    Titan Air's packaged DX units are designed using a conservative application of coil and blower manufacturers design recommendations to meet a customer's specific requirements. You can be assured of proper heating / cooling and airflow without paying for an undersized or oversized "standard" units. Multiple heating and humidity control options are available to suit jobsite gas, water, or power supplies. Standard temperature control options include discharge or room DDC control with optional building management interfaces or PLC controls for industrial or process applications.

    All heating and cooling components are factory wired, piped, and tested to make your jobsite installation as easy as possible. Multiple configurations and layouts are available for space or height restrictions. Custom condensing units are available for specific performance or construction requirements. Digital scroll compressors, modulating hot gas re-heat, and low acoustic options are available.

    The Titan Air packaged direct-fired and DX cooling unit combines the high efficiency of direct-fired heat with the convenience of packaged DX cooling. Direct-fired heat is 92% efficient and lower cost than indirect-fired heat. Standard equipment is available up to 14,000 CFM and 60 tons.

    Contact the factory for larger custom equipment.


    A) Outside Air Intake / Mixing Box
    Options include; 45° intake hood, hood filter combo, mushroom hood, wind driven rain louvers, and mixing boxes with flat or angled filters.

    B) High Quality & Performance Controls
    Flexible control sequences to meet customer requirements including DDC or PLC controls. Additional options include air flow monitoring station, and building management integration.

    C) Supply Fan / Power Return Fan
    Multiple optional fan configurations are available with additional options including air flow monitoring and vibration isolation.

    D) Factory Packaged Refrigeration
    Our high skilled employees take care of all wiring, piping, and refrigeration making the installation as simple and hassle free as possible.

    E) Dehumidification
    Optional modulating hot gas re-heat provides accurate and efficient method for controlling humidity using the excess heat from the refrigeration process. Additional options include electric, hot water or steam coils and indirect fired heat.

    F) Humidification
    Optional gas or electric steam generators can be added for humidification. Additional options include direct evaporative cooling.

    G) High Efficiency Heating
    Optional direct-fired burner is 92% efficient with a 25:1 turn down and is a lower cost that indirect-fired heat. Additional heating options include indirect-fired, electric, hot water, and steam.

    H) Commercial or Industrial Construction
    Multiple casing construction materials and components are available to meet the application requirements. Options include 2" double wall limited through metal construction and corrosion resistant construction.

    J) High Efficiency Final Filter Section
    Multiple filter combinations are available to achieve the customer indoor air quality requirements. Options include HEPA and carbon filters.

    K) Custom Air Cooled Condensing Unit
    Offers flexibility of condenser performance and controls. Additional options include modulating hot gas re-heat, low ambient operation, upgraded refrigeration components and special circuiting.

    L) Compressor Control
    Digital scroll compressors are available for greater cooling control and energy efficiency. Additional options include hot gas bypass for commercial applications.

    M) Low Ambient Operation
    Standard industrial equipment can operate to 20° F by condenser fan cycling. Additional options include variable air volume or flood control.